DM-1000 Electronic Trip Unit (Standard Unit)
Call for Price
Replace your existing STR Trip Unit with confidence using the fully programmable, retrofittable, DM-1000 Electronic Trip Unit.
The DM-1000 ETU replaces the Masterpact M OEM?s inherently faulty STR type trip units which, unfortunately, often suffer from non-repairable, spurious tripping problems. The DM-1000 is form-fit manufactured to make retro-fitting the trip unit device as easy and as fast as possible and utilises the existing current sensor connections of the Masterpact Air Circuit Breaker (ACB).
- Product Information
- Additional information
Product Information
Each of the five modelled ?STR? types contain all the protection functions, settings and options available to the original units so that the functionality and settings of the unit being replaced can be matched completely.
Available within the firmware (dependent on modelled unit selected) and hardware design are the following protection types:
Trip Units Modelled: DM18I / DM18M / DM28D / DM38S / DM58U
Long Time Protection Settings (Programmable)
LT Pick Up 0.4 to 1.0 x In
LT Time Delay 15 ? 480s
Short Time Protection Settings (Programmable)
ST Pick Up 1.5 to 10.0 x Ir
ST Time Delay 0.1 to 0.4s + I2t
Instantaneous Protection Settings (Programmable)
INST Pick Up 1.5 to 28.0 x In
Ground Fault Protection Settings (Programmable)
GF Pick Up 0.1 to 1.0 x Ir (or 1200A max)
GF Time Delay 0.1 to 0.4s + I2t
Phase Imbalance Protection Settings (Programmable)
PI Pick Up 0.25 to 0.70 x Ir
PI Time Delay 1 to 90s
Making Current Release / DINF Protection (Hardware based via dip switches on installation)
MCR Pick Up Set to breaker parameters
High Set Instantaneous Protection (Hardware based via dip switches on installation)
HSI Pick Up Set to breaker parameters